Call for Price: (800)-766-1212
Variant Cut Sheets
VIY-60 Unfused 2400/4160Y 7525A50G01 | VIY-60 Unfused 4200/4200Y 7525A50G02 | VIY-60 Unfused 4800/4800Y 7525A50G03
VIY-60 2 Fuses 2400/4160Y 7525A51G01 | VIY-60 2 Fuses 4200/4200Y 7525A51G02 | VIY-60 2 Fuses 4800/4800Y 7525A51G03
VIY-60 1 Fuse 2400/4160GY 7525A52G01 | VIY-60 1 Fuse 4200/4200GY 7525A52G02 | VIY-60 1 Fuse 4800/4800Y 7525A52G03
VIY-60 Switchgear Style 2400/4160Y 7525A54G01 | VIY-60 Switchgear Style 4200/4200Y 7525A54G02 | VIY-60 Switchgear Style 4800/4800Y 7525A54G03
VIY-60 Switchgear Style 2400/4160GY 7525A55G01 | VIY-60 Switchgear Style 4200/4200GY 7525A55G02 | VIY-60 Switchgear Style 4800/4800Y 7525A55G03
VIY-60 1 Fuse Non-indicating 2400/4160GY 9628A11G01 | VIY-60 1 Fuse Non-indicating 4200/4200GY 9628A11G02 | VIY-60 1 Fuse Non-indicating 4800/4800Y 9628A11G03
VIY-60 2 Fuses Non-indicating 2400/4160Y 9628A12G01 | VIY-60 2 Fuses Non-indicating 4200/4200Y 9628A12G02 | VIY-60 2 Fuses Non-indicating 4800/4800Y 9628A12G03
Product features
• 5 kV, indoor
• 60 kV BIL, 60 Hertz
• Primary volts: 2400 - 4800
• Approximate weights:- Unfused (with no provision for fuse mounting),
two bushings: 35 lbs (16 kg)- Unfused (with provision for fuse mounting),
two bushings: 35 lbs (16 kg)- Unfused (with provision for fuse mounting),
four bushings: 35 lbs (16 kg)- Fused (indicating), two bushings: 37 lbs (17 kg)- Fused (indicating), four bushings: 39 lbs (18 kg)- Fused (non-indicating), two bushings: 37 lbs
(17 kg)- Fused (non-indicating), four bushings: 39 lbs
(18 kg)
Construction features
The primary and secondary coils are wound using
special winding and shielding techniques for
improved voltage stress distribution. The coils are
designed to withstand continuous operation at 1.1
times the line-to-line voltage level and the line-to
ground voltage level for Y burden units. For some line
to-ground voltage units, a short-time withstand
voltage of 1.9 is available upon request.
Fuse classifications
This unit is provided with three fuse classifications:
mounted fuse with hardware, unfused with hardware,
or unfused without hardware. Optional fuse kits are
offered to convert some unfused styles to fused
styles. Consult your ABB sales representative
concerning overvoltage conditions for designs above
the standard rated voltage factor of 1.1.
Terminals
Compression-type primary terminals accommodate
#8 through #2 wire. Secondary brass terminal inserts
are 3/8” deep with a .190-32 tapped hole. Secondary
terminals are .190-32 compression screws.
A compression type terminal that accommodates #14
through #4 wire is provided on fused units on the line
end of each fuse.
Baseplate
The baseplate is constructed of corrosion-resistant
aluminum and secured to the encapsulated base
support.
Mounting
The VIY-60 can be mounted in upright, cantilever, or
upside-down positions.
Curves
Type curves are available upon request.
Test reports
Test reports are stored electronically and can be
e-mailed in various formats at the time of shipment.
Standards
This unit meets or exceeds all requirements of IEEE
C57.13-2016 and can be tested to other standards as
requested.
UL Recognized Component
The VIY-60 is a UL Recognized Component (file
number E148620).