Description
Call for Price: (800)-766-1212
Variant Cut Sheets
SCV-D 50:5 6353C89H01 | SCV-D 75:5 6353C89H02 | SCV-D 100:5 6353C89H03 | SCV-D 150:5 6353C89H04 | SCV-D 200:5 6353C89H05 | SCV-D 250:5 6353C89H06 | SCV-D 300:5 6353C89H07 | SCV-D 400:5 6353C89H08 | SCV-D 500:5 6353C89H09 | SCV-D 600:5 6353C89H10 | SCV-D 800:5 6353C89H11 | SCV-D 1000:5 6353C89H12 | SCV-D 1200:5 6353C89H13 | SCV-D 1500:5 6353C89H14 | SCV-D 2000:5 6353C89H15 | SCV-D 2500:5 6353C89H16 | SCV-D 3000:5 6353C89H17 | SCV-D 4000:5 6353C89H18
SCV-D Multi-Ratio 600 MR 6436C46H01 | SCV-D Multi-Ratio 1200 MR 6436C47H01 | SCV-D Multi-Ratio 2000 MR 6436C48H01 | SCV-D Multi-Ratio 3000 MR 6436C49H01 | SCV-D Multi-Ratio 4000 MR 6436C50H01
Product features
• 600 volt, indoor, 10 kV BIL
• 25 - 400 Hertz
• Mechanical rating: 180 x rated current
• Thermal rating: 80 x rated current, one second
• Approximate weight: 48 lbs (22 kg)
Application
The SCV-D deep case current transformer is suitable
for use in relaying and metering applications includ
ing, but not limited to, various types of medium volt
age switchgear. The increased depth allows for higher
metering and relaying burdens to be supported.
Construction features
The ring-type core is insulated and toroidally wound
with a fully distributed secondary winding. The pro
tective case, made of an impact-resistant polycarbon
ate, is assembled using self-tapping screws.
Secondary terminals
Secondary terminals are 10-32 brass terminal screws
with hardware. Space is available for a maximum of
five terminals to accommodate multi-ratio designs.
Curves
Excitation, overcurrent, and ratio correction factor
and phase-angle curves are available upon request.
Testing
IEEE test reports are stored electronically and can be
e-mailed in various formats at the time of shipment.
Standards
This unit meets all applicable IEEE and NEMA
standards.
UL Recognized Component
The SCV-D is a UL Recognized Component (file
number E96461).