Model Number: 120:5, Byram 2DRL121, Window with Terminals, Mounting Base
Ordering Number: 2DRL121
Technical Specifications
-
Primary currents: Up to 120 Amps
-
Secondary current: 5 amps
-
Frequency: 60hz
-
Inner diameter: 1.00" [25.4mm]
-
Outer diameter: 2.42" [61.47mm]
Application
Generally for ammeter use only
Frequency
50-400 Hz
Insulation Level
600 Volts, 10 kV BIL full wave
Rating Factor
2.0 @ 30°C amb.
General Information
Flexible leads are UL 1015, 105°C.
CSA approved.
#16 AWG, 24” long.
Non-standard length to be specified.
Terminals are brass studs No. 8-32 with one flat washer, lockwasher and regular nut.