Call for Price: (800)-766-1212
Variant Cut Sheets
BYZ 50:5 592C102G01 | BYZ 100:5 592C102G03
Product features
− 2500 volt test, indoor, 10 kV BIL
− 50-60 Hertz
− Primary amperes: 50 and 100
− Mechanical rating: 180 x rated current
− Thermal rating: 100 x rated current, 1 second
− Continuous current rating factor:
2.0 @ 30°C ambient
1.5 @ 55°C ambient
− Relay scheme: provided with unit dimensions
Application
The BYZ zero-sequence indoor current transformer is used for
ground fault detection and is primarily designed for zero-se
quence overcurrent relaying schemes. The outgoing cables pass
through the opening. A phase imbalance produces a secondary
current in the BYZ.
Construction features
The ring-type core is fully insulated and toroidally wound with a
fully distributed secondary winding.
Secondary terminals
Secondary terminals are electro-tin plated 10-32 tap terminals.
Curves
Saturation, overcurrent, ratio correction factor, and phase-angle
curves are available upon request.
Test reports
IEEE test reports are stored electronically and can be e-mailed
in various formats at the time of shipment.
Standards
This unit meets all applicable IEEE and NEMA standards.