Model 6528 is a low cost 1000V hand-held instrument that offers Multimeter functions as well as Megohmmeter functions. This model is created for the commercial, industrial and contractor markets and is simple to use. It's priced at a point tailored to contractors and independent electricians that need to check the quality of insulation as well as perform basic electrical measurements.
True Megohmmeter®
It is a True Megohmmeter®in compliance with IEC 61010 and is designed with features and functions for use in the field:
lightweight
compact
rugged
easy to handle, even when wearing gloves.
Its construction and interface is intended to simplify use. An intuitive pass/fail indication offering a blue/red backlight makes it very easy to identify defective conditions.
Automatic Test Inhibit for Safety
It includes an automatic test inhibit if connected to a live circuit as well as automatic discharge at the completion of the test.
DMR Functionality - Unique to AEMC
A relative measurement function called DMR, unique to AEMC, provides the capability to compare measurements to a known reference quickly recognizing potential problems. Multimeter functions include AC/DC voltage, resistance and continuity.
AC/DC Voltage Measurement
Range
700VACand 700VAC+DC
Accuracy
DC: ± (1% R + 1ct) AC+DC: ± (1.2% R + 1ct)
Resolution
1V
Frequency Range
DC & 30 to 440Hz
Input Impedance
25MΩ
Insulation Measurement
Test Voltage / Resistance Range
250V: 0.050MΩ to 4200MΩ 500V: 0.100MΩ to 4200MΩ 1000V: 0.20MΩ to 11.00GΩ
Measurement Accuracy
4MΩ/40MΩ/400MΩ: ± (1.5% R + 10ct) 4.2GΩ: ± (4% R + 10ct) 11GΩ: ± (10% R + 10ct) (1000V range)
Continuity Measurement
Ranges
0 to 40Ω (200mA test current ≤2Ω)
Accuracy
1.2% R + 3ct
Resolution max
0.01Ω
Leads compensation
Up to 5Ω
Threshold
Audible signal triggered Selectable ≤1 or 2Ω
Resistance Measurement
Range
0 to 420kΩ (Auto ranging)
Accuracy
± (1.2%R + 3ct)
Resolution max
0.1Ω
General Features
Time test
1 second to 39.59 minutes selectable
Display
LCD with backlight
Power Supply
Six AA batteries (NEDA 15A or IEC LR6)
Battery Life 5s ON, 25s OFF
>2000 measurement in MΩ, >300h in V AC/DC, >6000 measurement in Continuity Test