AEMC Ground Resistance Tester | Model 6417

AEMCOrdering #:2141.02
No reviews

Price:
Sale price$1,960.00
Stock:
Call (800) 766-1212 for current inventory and lead time

Description

Ground Resistance Measurement (Auto-Ranging 1 to 199Ω)
Measurement Range Resolution Accuracy
0.010 to 0.099Ω 0.001Ω ±(1.5%Reading +0.01Ω)
0.10 to 0.99Ω 0.01Ω ±(1.5%Reading +0.02Ω)
1 to 49.9Ω 0.1Ω ±(1.5% Reading +0.1Ω)
50.0 to 99.5Ω 0.5Ω ±(2% Reading +0.5Ω)
100 to 199Ω 1Ω ±(3% Reading +1Ω)
 200 to 395Ω 5Ω ±(5% Reading +5Ω)
400 to 590Ω 10Ω ±(10% Reading +10Ω)
 600 to 1150Ω 50Ω 20% approx.
1200 to 1500Ω 50Ω 25% approx.
Alarm Adjustable from 1 to 199Ω
Frequency Selection Choice of 50, 60, 128, or 2083Hz for impedance calculation
Maximum Overload Permanent current: 100 max. 50/60Hz
Transient current: (<5s) 200A 50/60Hz
Current  Measurement Range (Auto-Ranging)
Measurement Range Resolution Accuracy
0.200 to 0.999mA 1µA ±(2% Reading +50µA)
1.000 to 2.990mA 10µA ±(2% Reading +50µA)
3.00 to 9.99mA 10µA ±(2% Reading +50µA)
10.00 to 29.99mA 100µA ±(2% Reading +100µA)
30.0 to 99.9mA 100µA ±(2% Reading +100µA)
100 to 299.9mA 1mA ±(2% Reading +1mA)
0.300 to 0.990A 1mA ±(2% Reading +1mA)
1.000 to 2.999A 10mA ±(2% Reading +10mA)
3.00 to 39.99A 10mA ±(2% Reading +10mA)
Loop Inductance Measurement
Measurement range Resolution Accuracy
10 to 100µH 1µH ±(5% Reading +1µH)
100 to 500µH 1µH ±(3% Reading +1µH)
Contact Voltage (Touch Voltage) Calculated
Measurement range Resolution Accuracy
0.1 to 4.9V 0.1V ±(5% Reading +0.1V)
5.0 to 49.5V 0.5V ±(5% Reading +0.5V)
50 to 75.0V 1V ±(10% Reading +1V)
General Features
Display OLED, 152 segments 48x39mm
Memory 2000 measurements
Communication Bluetooth, DataView software included
Alarm 3 separate alarms (Ω, V and A)
Power Source 4x1.5V LR6 (AA) alkaline batteries or 4 NiMH batteries
Battery Life 12 hours or 1440 30-seconds tests approx.
Jaw Opening 1.38” (35mm) max
Dimensions 2.16 x 3.74 x 10.31” (55 x 95 x 262mm)
Weight (with Battery) 2.06 lbs (935g)
Operating Temperature -4° to +131°F (-20 to +55°C)
Storage Temperature -22° to +158°F (-30 to +70°C)
Relative Humidity Up to 90% @ 40°C
Ingress Protection (IP) IP 40
EMC EN 61326-1
Safety Compliance IEC 61010-1, EN 61010-2-30, EN 61010-2-32, Pollution Degree 2,  600V CAT IV Saftey icons for ETL and CE

Recently viewed