AEMC Megohmmeter | Model 6505

AEMCOrdering #:1A0320
No reviews

Price:
Sale price$2,850.00
Stock:
Call (800) 766-1212 for current inventory and lead time

Description

AC/DC Voltage Measurement
Range1 to 4000V
Accuracy1 to 99.9V: ±(1% R + 5ct)
100 to 4000V: ±(1% R + 3ct)
Resolution1 to 99.9V: 0.1V
100 to 999V: 1V
1000 to 4000V: 2V
Frequency Range1 to 2500V: DC or 15 to 500Hz
2501 to 4000V: DC
Input Impedance750kΩ or 3MΩ (range dependent)
Insulation Measurement
Test Voltage / Resistance Range500V: 10kΩ to 2TΩ
1000V: 10kΩ to 4TΩ
2500V: 10kΩ to 10TΩ
5000V: 10kΩ to 10TΩ
Measurement Accuracy10kΩ to 399.9GΩ: ±(5% R + 3ct)
400GΩ 10TΩ: ±(15% R + 10ct)
Variable Voltage40 to 5,100V
Auto DischargeDischarge time < 7s/µF from Vtest to 25V @ 5000V
Live Circuit IndicatorTest inhibition if terminal voltage > 40% of test voltage
General Features
Programmable AlarmYes
DAR – PIYes
Ramp ModeNo
Step ModeNo
Capacitance Measurement0.005 to 49.99µf
Open Circuit Voltage≤ 1.1 x Vn ±2V (Vn ±2% in variable mode)
Power SupplyRechargeable NIMH battery pack;
external 85-256V, 50/60Hz
Battery Life≥ 1500  tests at 5000V into 5MΩ with a duty cycle of 5 seconds on and 25 seconds off
Charging Time6 hours approximately (charging allowed during tests)
Dimensions10.63 x 9.84 x 7.09” (270 x 250 x 180mm)
Weight9.5 lbs (4.3kg)
Altitude Operating6562' (2000m)
Operating Temperature14° to +131°F (-10° to +55°C) ≤80% RH
Storage Temperature-40° to +158°F (-40° to +70°C) ≤90% RH
IP RatingIP 53
Safety ComplianceEN 61010-1, EN 61557, 1000V CAT III, Pollution Degree 2