AEMC Model 607 Clamp-On Meter
Model: AEMC 607 Clamp-on Meter
Part Number: 2139.61
Ordering Number: 1C0985
The TRMS Power Clamp-on Meter Model 607 provides a new standard for safety and measurement capability not available in any other clamp meter sold today. Safety Rated at 1000V CAT IV, it is safe to operate in most electrical environments. It is rugged enough for the most demanding work environments and will withstand both dust and water spray with its IP54 rating. It is ergonomically designed and easily used by one hand, including function selection and button pushing even with a glove on. In addition to the standard measurement of volts, amps, frequency, resistance, diode checking and continuity, the Model 607 offers several unequaled functions including: AC, DC and AC+DC volts, amps and power, True InRush®, power measurements, harmonic analysis, data logging, and more.
Voltage Range: | 1000Vrms AC/DC/AC+DC Autoranging |
Resolution Max: | 0.01V |
Current Range: | 2000Arms AC, 3000ADC |
Resolution Max: | 0.01A |
Accuracy V Typical: | 1% ± 3cts |
Accuracy A Typical: | 1% ± 3cts |
True InRush®: | 20 to 2000AAC, 20 to 3000ADC |
Power Measurement Max: | 2MW AC, 3MW DC |
Harmonics: | Up to 25th |
THD: | Yes, %f and %r |
Continuity: | Selectable from 0 to 999.9Ω |
Resistance: | 100kΩ |
Frequency: | 20kHz in V, 2kHz in A |
Power Factor: | Yes |
Phase Order: | Yes |
MIN/MAX/PEAK-/PEAK+ | Yes |
∆REL: | Yes |
Recording: | Yes, up to 1000 points (160 hours at 10 min intervals) |
Communication: | Bluetooth |
Software: | Yes, DataView included |
Power Source: | 4 x AA, NEDA 15A, IEC LR6 |
Battery Life: | >350 hours |
Dimensions: | 10.7 x 3.6 x 1.6" (272 x 92 x 41mm) |
Weight: | 1.4 lbs (640g) with batteries |
Jaw Opening: | 2.36" (60mm) |
Operating Temperature: | -4° to +131°F (-20 to +55°C) |
Storage Temperature: | -40° to +158°F (-40 to +70°C) |
Operating Humidity: | 90% up to 131°F (55°C) |
Pollution Degree: | 2 |
Ingress Protection: | IP54 |
EMC: | EN61326-1 |
Safety Compliance: | EN/IEC 61010-1 to 1000V CAT IV![]() EN/IEC 61010-2-030:2010 EN/IEC 61010-032:2002 |