Description
Inputs | 5 Voltage / 4 Current | ||||||
Sample Rate | 128 per Cycle | 6.4kHz at 50Hz | 7.68kHz at 60Hz | ||||
Specification | Range | Measurement Range | Resolution | Accuracy (Typical) | |||
Volt | |||||||
Vrms | 1000V P to N | 10 to 1000V | 0.1V | ±0.2% Rdg +0.2V | |||
Vrms | 1000V E to N | 10 to 1000V | 0.1V | ±0.2% Rdg +0.2V | |||
Urms | 1000V P to P | 17 to 1000V | 0.1V | ±0.2% Rdg + 0.4V | |||
Amps @ 50 and 60Hz | |||||||
Amps (1V nominal) (excluding clamp accuracy | Probe dependent | 0.2%< I < 120% Inom | Probe dependent | ±0.2% Rdg + 0.02% Inom | |||
AmpFLEX & MiniFlex (including sensor accuracy) | Range 100A Range 400A Range 2kA Range 10kA | 200mA to 120A 5 to 440A 50 to 2400A 400A to 12kA | 1mA 0.1A 0.1A & 1A 1A | ±1.2% Rdg + 50mA ±1.2% Rdg + 0.2A ±1.2% Rdg + 1A ±1.2% Rdg + 5A | |||
Frequency | 42.5 to 69Hz | 0.01Hz | ±0.1Hz | ||||
Power | |||||||
Watts (VA, var) P-Q-S | 20W to 20GW / 20var to 10Gvar / 20VA to 10GVA | 4 digits min | ±0.5% Rdg + 0.005% Pnom | ||||
Power Factor (Cos Φ/DPF) | -1 to 1 | 0.001 | ±0.05 | ||||
Energy | |||||||
kWh (kVAh, kvarh) P-Q-S | Up to 4EWh / 4Evarh / 4 EVAh (E = 1018 ) | ±0.5% Rdg | |||||
Harmonics | DC, 1 to 50 | ||||||
Volts & Amp % | 0.01 to 655.0% | 0.01% | ±1% Rdg from 1 to 25 | ||||
THD | 0.00 to 655.0% | 0.01% | ±1% Rdg | ||||
General Features | |||||||
Case | Design Rugged field case | ||||||
Interface | Isolated USB, Bluetooth, and Ethernet, Wi-Fi, SD card for direct transfer to PC. Dataview software for real time data, configuration and reporting included | ||||||
Memory | 8GB SD card (SDHC compliant, FAT32 formatted) 32GB max | ||||||
Display | LCD with backlight 4.2 x 3.3” (107 x 84mm) | ||||||
Real-Time Clock | Time and date stamp for Trend mode | ||||||
Power | Phase to phase or phase to neutral 100 to 1000VAC or external power pack 110V/230V 50/60Hz 15VA; Battery backup when power OFF, 60 minutes typical | ||||||
Dimensions (L x W x H) | 9.65 x 10.6 x 7.1” (245 x 270 x 180mm) | ||||||
Weight | 8.9 lbs (4kg) | ||||||
Altitude Operating | 2000m (6560ft) | ||||||
Operating Temperature | 32° to 108.5°F; (0° to +42.5°C) from 10 to 85% RH | ||||||
Storage Temperature | -4° to 122°F; (-20° to +50°C) from 0 to 75% RH with battery pack | ||||||
Electro-Magnetic-Compatibility (EMC) | EN 61326-1 for emission and immunity | ||||||
IP Rating | IP 67 per IEC 60529 | ||||||
Safety | IEC/EN 61010-1 (1000V CAT IV Pol 4) |
User Manuals
Modelo PEL 105 - Spanish (CA France version)
Model PEL 105 - French (CA France version)
Pole-Mounting-Kit: English, Spanish, and French (CA France version)
Quick Start Guides
Datasheets
Brochures
Comparison Charts
Software/Firmware
Ver. 3.61.0008 Open Release Notes for the latest updates | Models Supported by DataView
Release Date: November 12, 2019
DataView Complete (Report generation and control panels)
Executable: Version 3.61.0008 - .exe
Zipped File: 471MB Version 3.61.0008 - .zip
IMPORTANT:
- Back-up all template files before installation to ensure that they do not get overwritten.
- Uninstall previous versions of DataView before installing a new version.
- PQL Loggers and Sentinel Series are no longer supported by DataView. See bottom of the page for a compatible version
Supported Operating Systems:
Windows 7 (32 & 64 Bit)
Windows 8/8.1 (32 & 64 Bit)
Windows 10 (32 & 64 Bit)
Buy Test Equipment, Get Free Calibration
Free calibration on Test Equipment
Get free in-house calibration when you buy select test equipment from Byram labs.
Offer valid through 12/31/2021