Fluke 1587 FC 2-In-1 Insulation Multimeter
- Description
- Features
- Specifications
- Low-Pass Filter Voltage
- Measurement
- Testing
- Capacitance
- Insulation
- Output Voltage
- Other
Model: Fluke 1587 FC Insulation Multimeter
Part Number: 1587 FC
Ordering Number: 1C7454
The high-performance 2-in-1 insulation DMM
The Fluke 1587 FC Insulation Multimeters combine a digital insulation tester with a full-featured, true-rms digital multimeter in a single compact, handheld unit, which provides maximum versatility for both troubleshooting and preventative maintenance.
The Fluke 1587 FC Insulation Multimeter adds four powerful new diagnostic functions through the Fluke Connect® Measurements app:
- PI/DAR timed ratio tests with TrendIt™ graphs identifies moisture and contaminated insulation problems faster
- Memory storage through Fluke Connect eliminates writing down results, reduces errors and saves data for historical tracking over time
- Temperature Compensation through app for establishing accurate baselines and relevant historical comparisons
- Historical tracking and trending of assets identifies degradation over time, allows real-time decisions to be made in the field with Fluke Connect® Assets
Product highlights
- PI/DAR timed ratio tests
- Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection
- VFD low-pass filter for accurate motor drive measurements
- Auto-discharge of capacitive voltage for added user protection
- Insulation test (1587 FC: 0.01 MΩ to 2 GΩ)
- Insulation test voltages (1587 FC: 50 V, 100 V, 250 V, 500 V, 1000 V) for many applications
- AC/DC voltage, DC millivolts, AC/DC milliamps, Resistance (Ω), Continuity
- Capacitance, diode test, temperature, Min/Max, frequency (Hz)
- Auto power off to save battery power
- CAT III 1000 V, CAT IV 600 V measurement category
- Large display with backlight
- Rugged, utility hard case allows you to bring everything you need for the job
- Included accessories: Remote probe, test leads and probes, alligator clips, K-type thermocouple
- Accepts optional Fluke TPAK Magnetic Meter Hanger for convenient hands free operation
- Three-year standard warranty; extendable to five-years through product registration within 45 days of purchase
Includes:
- Remote probe
- Test leads
- Alligator clips
- K-type thermocouple
- Hard case
- User documentation
Size (H x W x L) | 5.0 x 10.0 x 20.3 cm (1.97 x 3.94 x 8.00 in) | |
Weight | 550 g (1.2 lb) |
- PI/DAR measurements with TrendIt™ graphs
- Memory storage through Fluke Connect Measurements app
- Temperature Compensation through Fluke Connect Measurements app
- VFD low-pass filter for accurate motor drive measurements
- Insulation test voltages 50 V, 100 V, 250 V, 500 V, 1000 V
- Insulation test: 0.01 MΩ to 2.0 GΩ
- Auto-discharge of capacitive voltage
- Insulation test smoothing reading
- Frequency
- Capacitance
- Diode test
- Temperature
- Min/Max
- AC/DC Voltage
- DC Millivolts
- AC/DC Milliamps
- Resistance (0.1 Ω to 50 MΩ)
- Continuity
- Three-year warranty
- Remote probe, test leads, alligator clips
- K-type thermocouple
- Rugged, utility hard case
- Auto power off
AC voltage measurement | ||
Range | ||
600.0 mV | Resolution | 0.1 mV |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts) | ±(2% + 3) | |
6.000 V | Resolution | 0.001 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts) | ±(2% + 3) | |
60.00 V | Resolution | 0.01 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts) | ±(2% + 3) | |
600.0 V | Resolution | 0.1 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts) | ±(2% + 3)¹ | |
1000 V | Resolution | 1 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(2% + 3) | |
Accuracy 60 Hz to 5000 Hz ±(% of Rdg + Counts) | ±(2% + 3)¹ | |
¹ 1 kHz bandwidth |
Range | ||
600.0 mV | Resolution | 0.1 mV |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts) | +(2% + 3), -(6% - 3) | |
6.000 V | Resolution | 0.001 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts) | +(2% + 3), -(6% - 3) | |
60.00 V | Resolution | 0.01 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts) | +(2% + 3), -(6% - 3) | |
600.0 V | Resolution | 0.1 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(1% + 3) | |
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts) | +(2% + 3), -(6% - 3) | |
1000 V | Resolution | 1 V |
Accuracy 50 Hz to 60 Hz ±(% of Rdg + Counts) | ±(2% + 3) | |
Accuracy 60 Hz to 400 Hz ±(% of Rdg + Counts) |
DC Voltage Measurement | ||
Range | Resolution | Accuracy ±(% of Rdg + Counts) |
6.000 V dc | 0.001 V | ±(0.09% + 2) |
60.00 V dc | 0.01 V | ±(0.09% + 2) |
600.0 V dc | 0.1 V | ±(0.09% + 2) |
1000 V dc | 1 V | ±(0.09% + 2) |
Input impedance | 10 MΩ (nominal), <100 pF | |
Normal mode rejection ratio | >60 dB @ 50 Hz or 60 Hz | |
Common mode rejection ratio | >120 dB @ dc, 50 Hz or 60 Hz (1 k unbalance) | |
Accuracies apply to ± 100% of range | ||
DC Millivolts Measurement | ||
Range | Resolution | Accuracy ±(% of Rdg + Counts) |
600.0 mVdc | 0.1 mV | ±(0.1% + 1) |
DC and AC Current Measurement | ||
AC 45 Hz to 1000 Hz | ||
Range | 400 mA | |
Resolution | 0.1 mA | |
Accuracy ±(% of Rdg+Counts) | ±(1.5% + 2)¹ | |
Burden voltage (Typical) | 2 mV/mA | |
Range | 60 mA | |
Resolution | 0.01 mA | |
Accuracy ±(% of Rdg+Counts) | ±(1.5% + 2)¹ | |
Burden voltage (Typical) | 2 mV/mA | |
DC | ||
Range | 400 mA | |
Resolution | 0.1 mA | |
Accuracy ±(% of Rdg+Counts) | ±(0.2% + 2) | |
Burden voltage (Typical) | 2 mV/mA | |
Range | 60 mA | |
Resolution | 0.01 mA | |
Accuracy ±(% of Rdg+Counts) | ±(0.2% + 2) | |
Burden voltage (Typical) | 2 mV/mA | |
Overload | 600 mA for 2 minutes maximum | |
Fuse protection for mA input | 0.44 mA, 1000 V, IR 10 kA | |
AC conversion | Inputs are ac-coupled and calibrated to the rms value of sine wave input | |
Conversions are true-rms responding and specified from 5% to 100% of range. Input signal crest factor can be up to 3 up to 300 mA, decreasing linearly to crest factor ≤1.5 at 600 mA. For non-sinusoidal waveforms add +(2% reading + 2% FS) typical, for a crest factor up to 3. | ||
¹ 1 kHz bandwidth | ||
Ohms Measurement | ||
Range | Resolution | Accuracy +(% of Rdg+Counts)¹ |
600.0 Ω | 0.1 Ω | ±(0.9% + 2) |
6.000 kΩ | 0.001 kΩ | ±(0.9% + 2) |
60.00 kΩ | 0.01 kΩ | ±(0.9% + 2) |
600.0 kΩ | 0.1 KΩ | ±(0.9% + 2) |
6.000 MΩ | 0.001 MΩ | ±(0.9% + 2) |
50.0 MΩ ² | 0.01 MΩ | ±(1.5% + 3) |
Overload protection | 1000 V rms or dc | |
Open circuit test voltage | <8.0 V dc | |
Short circuit current | <1.1 mA | |
¹ Accuracies apply from 0% to 100% of range ² Up to 80% relative humidity |
Frequency Measurement | ||
Range | Resolution | Accuracy ±(% of Rdg+Counts) |
99.99 Hz | 0.01 Hz | ±(0.1% + 1) |
999.9 Hz | 0.1 Hz | ±(0.1% + 1) |
9.999 kHz | 0.001 kHz | ±(0.1% + 1) |
99.99 kHz | 0.01 kHz | ±(0.1% + 1) |
Temperature Measurement | ||
Range | Resolution | Accuracy ±(% of Rdg+Counts)¹ |
-40 ° C to 537 ° C | 0.1 °C | ±(1% + 10 counts) |
-40 ° F to 998 ° F | 0.1 °F | ±(1% + 18 counts) |
¹ Accuracies apply following 90 minutes settling time after a change in the ambient temperature of the instrument |
Diode Test | ||
Diode test indication | Display voltage drop: 0.6 V at1.0 mA nominal test current: | |
Accuracy | ±(2% + 3) | |
Continuity Test | ||
Continuity indication | Continuous audible tone for testresistance below 25 Ω and off above 100 Ω. Maximum Reading; 1000 Ω | |
Open circuit voltage | <8.0 V | |
Short circuit current | 1.0 mA typical | |
Overload protection | 1000 V rms | |
Response time | >1 m sec |
Range | Resolution | Accuracy ±(% of Rdg+Counts) |
1000 nF | 1 nF | ±(1.2% + 2) |
10.00 μF | 0.01 μF | ±(1.2% + 2) |
100.0 μF | 0.1 μF | ±(1.2% ±90 counts) |
9999 μF | 1 μF | ±(1.2% ±90 counts) |
Measurement range | 0.01 MΩ to 2 GΩ | |
Test voltages | 50, 100, 250, 500, 1000 V | |
Test voltage accuracy | +20%, -0% | |
Short-circuit test current | 1 mA nominal | |
Auto discharge | Discharge time <0.5 second for C = 1 μF or less | |
Live circuit detection | Inhibit test if terminal voltage > 30 V prior to initialization of test | |
Maximum capacitive load | Operable with up to 1 μF load |
50 V (0% to +20%) | Display range | 0.01 to 6.00 MΩ |
Resolution | 0.01 MΩ | |
Test current | 1 mA @ 50 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(3% + 5 counts) | |
Display range | 6.0 to 50.0 MΩ | |
Resolution | 0.1 MΩ | |
Test current | 1 mA @ 50 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(3% + 5 counts) | |
100 V (0% to +20%) | Display range | 0.01 to 6.00 MΩ |
Resolution | 0.01 MΩ | |
Test current | 1 mA @ 100 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(3% + 5 counts) | |
Display range | 6.0 to 60.0 MΩ | |
Resolution | 0.1 MΩ | |
Test current | 1 mA @ 100 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(3% + 5 counts) | |
Display range | 60 to 100 MΩ | |
Resolution | 1 MΩ | |
Test current | 1 mA @ 100 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(3% + 5 counts) | |
250 V (0% to +20%) | Display range | 0.1 to 60.0 MΩ |
Resolution | 0.1 MΩ | |
Test current | 1 mA @ 250 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(1.5% + 5 counts) | |
Display range | 60 to 250 MΩ | |
Resolution | 1 MΩ | |
Test current | 1 mA @ 250 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(1.5% + 5 counts) | |
500 V (0% to +20%) | Display range | 0.1 to 60.0 MΩ |
Resolution | 0.1 MΩ | |
Test current | 1 mA @ 500 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(1.5% + 5 counts) | |
Display range | 60 to 500 MΩ | |
Resolution | 1 MΩ | |
Test current | 1 mA @ 500 kΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(1.5% + 5 counts) | |
1000 V (0% to +20%) | Display range | 0.1 to 60.0 MΩ |
Resolution | 0.1 MΩ | |
Test current | 1 mA @ 1 MΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(1.5% + 5 counts) | |
Display range | 60 to 600 MΩ | |
Resolution | 1 MΩ | |
Test current | 1 mA @ 1 MΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(1.5% + 5 counts) | |
Display range | 0.6 to 2.0 GΩ | |
Resolution | 100 MΩ | |
Test current | 1 mA @ 1 MΩ | |
Resistance accuracy ±(% of Rdg + Counts) | ±(10% + 3 counts) |
Maximum voltage applied to any terminal and common | 1000 V | |
Storage temperature | -40 °C to 60 °C (-40 °F to 140 °F) | |
Operating temperature | -20 °C to 55 °C (-4 °F to 131 °F) | |
Temperature coefficient | 0.05 x (specified accuracy) per °C for temperatures <18 °C or >28 °C (<64 °F or >82 °F) | |
Relative humidity | Noncondensing | |
0% to 95% @ 10 °C to 30 °C (50 °F to 86 °F) | ||
0% to 75% @ 30 °C to 40 °C (86 °F to 104 °F) | ||
0% to 40% @ 40 °C to 55 °C (104 °F to 131 °F) | ||
Vibration | Random, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument | |
Radio frequency communication | 2.4 GHz ISM Band | |
Radio frequency certification | FCC: T68-FBLE, IC: 6627A-FBLE |