The True RMS Clamp-On Meter Model 205 is safety rated at 600V CAT IV. It measures AC+DC volts and amps, frequency, continuity, resistance, power and Power Factor, phase rotation, and THD. It can also perform diode checks. The Delta relative function compares new measurements to a reference value, and the MIN/MAX function tracks high and low values. The Model 205 also tracks peak+ and peak– values. This compact and rugged meter can operate in demanding work environments.
Voltage Range:
1000Vrms AC/DC/AC+DC Auto-ranging
Resolution Max:
0.01V
Current Range:
600Arms AC, 900ADC
Resolution Max:
0.01A
Accuracy V Typical:
1% ± 3cts
Accuracy A Typical:
1% ± 3cts
InRush:
6 to 600AAC, 6 to 900ADC
Power Measurement Max:
600kW AC, 900kW DC
THD:
Yes, %f and %r
Continuity:
Selectable from 0 to 599.9Ω
Resistance:
60kΩ
Diode Test:
0 to 3.2VDC
Frequency:
20kHz in V, 3kHz in A
Power Factor:
Yes
Phase Order:
Yes
MIN/MAX/PEAK-/PEAK+
Yes
∆REL:
Yes
Power Source:
1 x 9V, IEC LF22
Battery Life:
>120 hours
Dimensions:
8.7 x 3.0 x 1.65" (222 x 78 x 42mm)
Weight:
12.0 oz. (340g) with battery
Jaw Opening:
1.34" (34mm)
Operating Temperature:
-4° to +131°F (-20 to +55°C)
Storage Temperature:
-40° to +158°F (-40 to +70°C)
Operating Humidity:
90% up to 131°F (55°C)
Pollution Degree:
2
Ingress Protection:
IP40
EMC:
EN61326-1
Safety Compliance:
EN/IEC 61010-1: 1000V CAT III, 600V CAT IV EN/IEC 61010-2-030:2010 EN/IEC 61010-032:2002