AEMC Model 6505 Megohmmeter

AEMC

$2,550.00 
SKU: 1A0320

Model: 6505 Megohmmeter

Part Number: 2130.18

Ordering Number: 1A0320

Datasheet

The Megohmmeter Model 6505 is a True Megohmmeter® portable instrument housed in a rugged field case that operates on either battery or line power. It performs voltage, insulation, and capacitance measurements. This instrument contributes to the safety of electrical installations and equipment.

Features include automatic calculation and presentation of the Dielectric Absorption Ratio (DAR) and Polarization Index (PI). The Model 6505 displays the test voltage, insulation resistance and the leakage current during the test. Capacitance of the sample and discharge voltage present at the test leads is displayed at the conclusion of the test.

The Model 6505 is designed with a high level of built-in safety features. This meter incorporates test inhibit capabilities which will not allow test voltages to be generated if a live sample is detected. The test terminals are recessed to ensure operating safety. 

Programmable Alarm Yes
DAR – PI Yes
Ramp Mode No
Step Mode No
Capacitance Measurement 0.005 to 49.99µf
Open Circuit Voltage ≤ 1.1 x Vn ±2V (Vn ±2% in variable mode)
Power Supply Rechargeable NIMH battery pack;
external 85-256V, 50/60Hz
Battery Life ≥ 1500  tests at 5000V into 5MΩ with a duty cycle of 5 seconds on and 25 seconds off
Charging Time 6 hours approximately (charging allowed during tests)
Dimensions 10.63 x 9.84 x 7.09” (270 x 250 x 180mm)
Weight 9.5 lbs (4.3kg)
Altitude Operating 6562' (2000m)
Operating Temperature 14° to +131°F (-10° to +55°C) ≤80% RH
Storage Temperature -40° to +158°F (-40° to +70°C) ≤90% RH
IP Rating IP 53
Safety Compliance EN 61010-1, EN 61557, 1000V CAT III, Pollution Degree 2

 

Range 1 to 4000V
Accuracy 1 to 99.9V: ±(1% R + 5ct)
100 to 4000V: ±(1% R + 3ct)
Resolution 1 to 99.9V: 0.1V
100 to 999V: 1V
1000 to 4000V: 2V
Frequency Range 1 to 2500V: DC or 15 to 500Hz
2501 to 4000V: DC
Input Impedance

750kΩ or 3MΩ (range dependent)

 

 

Test Voltage / Resistance Range 500V: 30kΩ to 2TΩ
1000V: 100kΩ to 4TΩ
2500V: 100kΩ to 10TΩ
5000V: 300kΩ to 10TΩ
Measurement Accuracy 30kΩ to 39.99GΩ: ±(5% R + 3ct)
40.0GΩ 10TΩ: ±(15% R + 10ct)
Variable Voltage 40 to 5,100V
Auto Discharge Discharge time < 7s/µF from Vtest to 25V @ 5000V
Live Circuit Indicator Inhibit test if terminal voltage > 25V prior to initialization of test

Our Partners