AEMC Simple Logger® II Model ML912

Save $36.45
AEMCOrdering #:1A0279
No reviews

Price:
Sale price$692.55 Regular price$729.00
Stock:
Call (800) 766-1212 for current inventory and lead time

Description

ChannelsTwo
InputCaptive MiniFlex AC current flexible sensor
Ranges (2)1 to 100AAC & 5 to 1000AAC
Accuracy (50/60Hz)1 to 100A ±(1% R +0.5A)
5 to 1000A (1% R +1A)
Resolution0.1A
Maximum Input Current600A < 1 min.
Sample Rate64 samples / cycle
Storage RateProgrammable from 125ms to 1 per day
Storage ModesStart/Stop, FIFO,  extended mode (XRM) and Alarm
Recording Length15 minutes to 6 weeks, programmable with DataView software
Memory240,000 measurements (512KB). Recorded data is stored in non-volatile memory and will be retained even if battery is low or removed.
CommunicationUSB 2.0 optically isolated
Power Source2x1.5V AA (LR6) alkaline batteries
Battery Life100 hrs to >45 days (depending of sample rate/recording length)
Dimensions4.95 x 2.75 x 1.28” (136 x 70 x 32mm) w/o sensor
Sensor/Cable LengthSensor: 6” (152mm) / Cable: 6 ft. (2m)
Weight (with battery)8.67 oz (245g)
CasePolycarbonate
Maximum Conductor Size        Ø 1.77” (45mm)
Operating Temperature14° to 122°F (-10° to 50°C)
Storage Temperature-4° to 140°F (-20° to 60°C)
Relative HumidityUp to 85% @ 95°F (35°C)
Ingress Protection (IP)IP40
EMCEN 61326-1
Safety ComplianceIEC 61010-1, EN 61010-2-32 600V CAT IV Pollution Degree 2

User Manuals

Simple Logger II - English

Simple Logger II Multi-lingual (CA France version)

Quick Start Guides

Simple Logger II

Datasheets

Model ML912 - English

Modelo ML912 - Spanish

Comparison Charts

Data Logger - Probe Selection Chart

Registradores de datos - Tabla de selecction de sondas

Software/Firmware

DataView Software

Ver. 3.61.0008   Open Release Notes for the latest updates   |   Models Supported by DataView
Release Date: November 12, 2019

DataView Complete (Report generation and control panels)
Executable: Version 3.61.0008 - .exe
Zipped File: 471MB Version 3.61.0008 - .zip

IMPORTANT:

  • Back-up all template files before installation to ensure that they do not get overwritten.
  • Uninstall previous versions of DataView before installing a new version.
  • PQL Loggers and Sentinel Series are no longer supported by DataView. See bottom of the page for a compatible version

Supported Operating Systems:
Windows 7 (32 & 64 Bit)
Windows 8/8.1 (32 & 64 Bit)
Windows 10 (32 & 64 Bit)

Click here for the Minimum System Requirements