Case | Design Rugged, shock proof with integrated protective holster Drip and dust proof IP51 according to IEC60529 when used in tilt stand position Shock and vibration Shock 30 g, vibration: 3 g sinusoid, random 0.03 g 2 /Hz according to MIL-PRF-28800F Class 2 | |||
Display | Brightness: 200 cd/m 2 typ. using power adapter, 90 cd/m 2 typical using battery power Size: 127 x 88 mm (153 mm/6.0 in diagonal) LCD Resolution: 320 x 240 pixels Contrast and brightness: user-adjustable, temperature compensated | |||
Memory | 8GB SD card (SDHC compliant, FAT32 formatted) standard, upto 32 GB optionally Screen save and multiple data memories for storing data including recordings (dependent on memory size) | |||
Real-Time Clock | Time and date stamp for Trend mode, Transient display, System Monitor and event capture |
Drive Measurement
Motor Type | 3 phase asynchronous (induction) | |||
Power Source | Variable Frequency Drive | |||
Motor Frequency Range | 40Hz to 70Hz | |||
Over/Under Voltage from Nominal V/f Curve (%) | -15% to +15% | |||
Carrier Frequency Range | 2.5kHz–20kHz |
Variable speed drive technology that is covered by the 438-II
Inverter Type | VSI only (voltage controlled) * | |||
Control Method | V/f control, open-loop vector, closed loop vector, drives with encoders | |||
Frequency | 40 to 70 Hz | |||
* VSI drives are the most common drives. The alternative CSI drives are used in higher power applications. |
Variable speed drive technology NOT covered by the 438-II
Inverter Type | CSI (current source inverter) | |||
Motors type | Synchronous (DC, stepper, permanent magnet etc.) | |||
Motor Frequency | <40 and >70 Hz |
Motor measurement
Range | Resolution | Accuracy | Default limit | |
Mechanical motor Power | 0.7 kW to 746 kW 1 hp to 1000 hp | 0.1 kW 0.1 hp | ±3%1 ±3%1 | 100% = rated power 100% = rated power |
Torque | 0 Nm to 10 000 Nm 0 lb ft to 10 000 lb ft | 0.1 Nm 0.1 lb ft | ±5%1 ±5%1 | 100% = rated torque 100% = rated torque |
rpm | 0 rpm to 3600 rpm | 1 rpm | ±3%1 | 100% = rated rpm |
Efficiency | 0% to 100% | 0.10% | ±3%1 | NA |
Unbalance (NEMA) | 0% to 100% | 0.10% | ±0.15% | 5% |
Harmonics Voltage Factor (NEMA) | 0 to 0.20 | 0.1 | ±1.5% | 0.15 |
Unbalance Derating Factor | 0.7 to 1.0 | 0.1 | indicative | NA |
Harmonics Derating Factor | 0.7 to 1.0 | 0.1 | indicative | NA |
Total NEMA Derating Factor | 0.5 to 1.0 | 0.1 | indicative | NA |
Notes: | Supports motor design types NEMA A, B, C, D & E and IEC type H and N. Rated torque is calculated from rated power and rated speed. Update rate of Motor Measurements is 1x per second. Default Trend duration is 1 week. | |||
1Add 5% error when selecting Motor design type Other Specification valid for Motor Power > 30% of rated power Specification valid at stable operating temperature. Run the motor for at least 1 hour at full load (2-3 hours if the motor is 50 HP or higher) to obtain stable temperature |
Product Specifications
Volt | Model | Measurement Range | Resolution | Accuracy |
Vrms (AC + DC) | 1 V to 1000 V phase to neutral | 0.01 V | ±0.1% of nominal voltage1 | |
Vpk | 1 Vpk to 1400 Vpk | 1 V | 5% of nominal voltage | |
Voltage Crest Factor (CF) | 1.0 > 2.8 | 0.01 | ±5% | |
Vrms½ | 0.1 V | ±0.2% of nominal voltage | ||
Vfund | 0.1 V | ±0.1% of nominal voltage |
Amps
Amps (accuracy excluding clamp accuracy)
Amps (AC + DC) | i430-Flex 1x | 5 A to 6000 A | 1 A | ±0.5% ±5 counts |
i430-Flex 10x | 0.5 A to 600 A | 0.1 A | ±0.5% ±5 counts | |
1mV/A 1x | 5 A to 2000 A | 1A | ±0.5% ±5 counts | |
1mV/A 10x | 0.5 A A to 200 A (AC only) | 0.1 A | ±0.5% ±5 counts | |
Apk | i430-Flex | 8400 Apk | 1 Arms | ±5% |
1mV/A | 5500 Apk | 1 Arms | ±5% | |
A Crest Factor (CF) | 1 to 10 | 0.01 | ±5% | |
Amps½ | i430-Flex 1x | 5 A to 6000 A | 1 A | ±1% ±10 counts |
i430-Flex 10x | 0.5 A to 600 A | 0.1 A | ±1% ±10 counts | |
1mV/A 1x | 5 A to 2000 A | 1 A | ±1% ±10 counts | |
1mV/A 10x | 0.5 A A to 200 A (AC only) | 0.1 A | ±1% ±10 counts | |
Afund | i430-Flex 1x | 5 A to 6000 A | 1 A | ±0.5% ±5 counts |
i430-Flex 10x | 0.5 A to 600 A | 0.1 A | ±0.5% ±5 counts | |
1mV/A 1x | 5 A to 2000 A | 1 A | ±0.5% ±5 counts | |
1mV/A 10x | 0.5 A A to 200 A (AC only) | 0.1 A | ±0.5% ±5 counts |
Hz
Fluke 434 @ 50 Hz Nominal | 42.50 Hz to 57.50 Hz | 0.01 Hz | ±0.01 Hz | |
Fluke 434 @ 60 Hz Nominal | 51.00 Hz to 69.00 Hz | 0.01 Hz | ±0.01 Hz |
Power
Watts (VA, var) | i430-Flex | max 6000 MW | 0.1 W to 1 MW | ±1% ±10 counts |
1 mV/A | max 2000 MW | 0.1 W to 1 MW | ±1% ±10 counts | |
Power Factor (Cos j/DPF) | 0 to 1 | 0.001 | ±0.1% @ nominal load conditions |
Energy
kWh (kVAh, kvarh) | i430-Flex 10x | Depends on clamp scaling and V nominal | ±1% ±10 counts | |
Energy Loss | i430-Flex 10x | Depends on clamp scaling and V nominal | ±1% ±10 counts Excluding line resistance accuracy |
Harmonics
Harmonic Order (n) | DC, 1 to 50 Grouping: Harmonic groups according to IEC 61000-4-7 | |||
Inter-Harmonic Order (n) | OFF, 1 to 50 Grouping: Harmonic and Interharmonic subgroups according to IEC 61000-4-7 | |||
Volts % | f | 0.0% to 100% | 0.1% | ±0.1% ±n x 0.1% |
r | 0.0% to 100% | 0.1% | ±0.1% ±n x 0.4% | |
Absolute | 0.0 to 1000 V | 0.1 V | ±5%1 | |
THD | 0.0% to 100% | 0.1% | ±2.5% | |
Amps % | f | 0.0% to 100% | 0.1% | ±0.1% ±n x 0.1% |
r | 0.0% to 100% | 0.1% | ±0.1% ±n x 0.4% | |
Absolute | 0.0 to 600 A | 0.1 A | ±5% ±5 counts | |
THD | 0.0% to 100% | 0.1% | ±2.5% | |
Watts % | f or r | 0.0% to 100% | 0.1% | ±n x 2% |
Absolute | Depends on clamp scaling and V nominal | — | ±5% ±n x 2% ±10 counts | |
THD | 0.0% to 100% | 0.1% | ±5% | |
Phase Angle | -360° to +0° | 1° | ±n x 1° |
The ideal portable motor analysis test tool, the 438-II can help locate, predict, prevent, and troubleshoot power quality problems in three-phase and single-phase power distribution systems, while giving technicians the mechanical and electrical information they need to effectively evaluate motor performance.
- Measure key parameters like speed, torque and mechanical power without mechanical sensor all while the motor is in service simply by using three-phase input measurements
- Calculate Mechanical Power and Efficiency without the need of mechanical sensors
- Automatically calculate motor derating according to NEMA/IEC guidelines
- Measure electrical power parameters such as voltage, current, power, apparent power, power factor, harmonic distortion and unbalance to identify characteristics that impact motor efficiency
- PowerWave data technology captures fast RMS data, and shows half-cycle averages and waveforms to characterize electrical system dynamics (generator start-ups, UPS switching etc.)
- Identify power quality issues such as dips, swells, transients, harmonics and unbalance
- Waveform capture function captures 100/120 cycles (50/60 Hz) of each event detected event, in all modes, without set-up
- Automatic transient mode captures waveform data at 200 kS/s on all phases simultaneously up to 6 kV
- Fluke Connect® compatible* – view data locally on the instrument, via Fluke Connect mobile app and PowerLog 430-II desktop software
- Highest safety rating in the industry: 600 V CAT IV/1000 V CAT III rated for use at the service entrance.
Buy Test Equipment, Get Free Calibration
Free calibration on Test Equipment
Get free in-house calibration when you buy select test equipment from Byram labs.
Offer valid through 12/31/2021